ADSS optical cable suspension clamp
Suspension fittings include ADSS optical cable suspension fittings and OPGW suspension fittings. OPGW optical cable suspension fittings have one more ground wire than ADSS optical cable suspension fittings, which are produced according to the cable diameter and tensile strength of the optical cable.
According to the different connecting parts used for poles and towers, different models can also be equipped.
Suspension string fittings include U-shaped screws, suspension clamps, pre-twisted wire protection lines, grounding drain wires and necessary connection fittings.
The mechanical strength of the hanging string connection fittings is 70kN.
The suspension clamp is a pre-twisted wire type, and the clamp body is made of aluminum alloy. The clamp body should be equipped with an EPDM rubber cushioning elastic pad.
The allowable value of the drape angle at the outlet of the OPGW single drape clamp is not less than 15 degrees. The ground wire is connected to the wire clamp of the tower, and its screw hole needs to be matched with the M16 bolt. The heat capacity of the ground wire should match the OPGW.
Product composition diagram:
Product technical specification sheet:
Sn | Model No. | Suitable cable range(mm) | Inner rod | Outer rods |
1 | OCL 0800 | 7.4-8.0 | Aluminum alloy wire Φ3.7 | Aluminum alloy wire Φ5.18 |
2 | OCL 0880 | 8.1-8.8 | ||
3 | OCL 0960 | 8.9-9.6 | ||
4 | OCL 1010 | 9.7-10.1 | ||
5 | OCL 1060 | 10.2-10.6 | ||
6 | OCL 1110 | 10.7-11.1 | ||
7 | OCL 1160 | 11.2-11.6 | ||
8 | OCL 1170 | 11.7 | Aluminum alloy wire Φ4.3 | Aluminum alloy wire Φ6.3 |
9 | OCL 1200 | 11.8-12.0 | ||
10 | OCL 1270 | 12.1-12.7 | ||
11 | OCL 1290 | 12.8-12.9 | ||
12 | OCL 1360 | 13.0-13.6 | ||
13 | OCL 1410 | 13.7-14.1 | ||
14 | OCL 1430 | 14.2-14.3 | ||
15 | OCL 1450 | 14.4-14.5 | ||
16 | OCL 1510 | 14.6-15.1 | ||
17 | OCL 1580 | 15.2-15.8 | ||
18 | OCL 1600 | 15.9-16.0 | ||
19 | OCL 1690 | 16.1-16.9 | ||
20 | OCL 1730 | 17.0-17.3 | ||
21 | OCL 1800 | 17.4-18.0 | ||
22 | OCL 1840 | 18.1-18.4 |
Safety Note
It must be ensured that the extreme contact pressure under the fitting does not exceed the extrusion design limit of the ADSS optical cable. In the use of the tension value, it is necessary to ensure that the ADSS optical cable and the wire do not whip, and the load on the tower is as small as possible to avoid safety problems.